Test
Seq. |
Item |
Requirements Acc. To EN50393 |
Results |
Remarks EN50393 |
1 |
Impulse withstand voltage test |
No breakdown shall occur at 10 positive and 10 negative
impulses of 20kV |
No Breakdown shall occur at 10 positive and 10 negative
impulses of 20kV |
PASS |
2 |
AC withstand voltage test (in air and ambient temperature) |
4kV, 1min, No breakdown |
4kV, 1min, No breakdown |
PASS |
3 |
Insulation resistance (in air and ambient temperature) |
>50MΩ |
>50MΩ |
PASS |
4 |
Impact test (in air and ambient temperature) |
4kg wedge dropped from a height of 1000mm |
4kg wedge dropped from a height of 1000mm |
PASS |
5 |
AC withstand voltage test immersed in the water with a height
of 1000mm |
4kV, 1min, No breakdown |
4kV, 1min, No breakdown |
PASS |
6 |
Heating cycle test (immersed in the water with a height of
1000mm) |
Heat the conductor to 95oC-100oC, 60 times in the
water, No breakdown |
Heat the conductor to 95oC-100oC, 60 times in the water, No
breakdown |
PASS |